Select conduit type and size, then add conductors. NEC Chapter 9, Tables 4 & 5 limits: 53% for 1 wire, 31% for 2 wires, 40% for 3+ wires.
| Conduit Size | Type | Total Area (in²) | 40% Fill (in²) | 31% Fill (in²) | 53% Fill (in²) |
|---|
| AWG / kcmil | Area (in²) | Diameter (in) | Common Use |
|---|---|---|---|
| #14 | 0.0097 | 0.111 | 15A circuits, control wiring |
| #12 | 0.0133 | 0.130 | 20A circuits, general purpose |
| #10 | 0.0211 | 0.164 | 30A circuits, HVAC feeders |
| #8 | 0.0366 | 0.216 | 40–50A, dryers, small feeders |
| #6 | 0.0507 | 0.254 | 55–65A, panel feeders |
| #4 | 0.0824 | 0.324 | 70–85A, sub-panel feeders |
| #3 | 0.0973 | 0.352 | 85–100A feeders |
| #2 | 0.1158 | 0.384 | 95–115A, service entrance |
| #1 | 0.1562 | 0.446 | 110–130A, large feeders |
| #1/0 | 0.1855 | 0.486 | 125–150A, service entrance |
| #2/0 | 0.2223 | 0.532 | 145–175A, main feeders |
| #3/0 | 0.2679 | 0.584 | 165–200A, main feeders |
| #4/0 | 0.3237 | 0.642 | 195–230A, service entrance |
| 250 kcmil | 0.3970 | 0.711 | 215–255A, large service |
| 300 kcmil | 0.4608 | 0.766 | 240–285A, large service |
| 350 kcmil | 0.5242 | 0.817 | 260–310A, large feeders |
| 400 kcmil | 0.5863 | 0.864 | 280–335A |
| 500 kcmil | 0.7073 | 0.949 | 320–380A, large feeders |
| 600 kcmil | 0.8659 | 1.051 | 355–420A |
| 750 kcmil | 1.0496 | 1.156 | 400–475A, utility primary |